Description
Purpose: temperature measurement with thermocouples Connection : 8 differential channels of analogue input signals of thermocouple types: J (TJK), K (TCA), B (TPR), L (TCC), E (TCCn), S (TPP 10%),R (TPP 13%), N (TNN), T (TMK), A-1 (TWR), A-2 (TWR), A-3 (TWR) Digit capacity: 16 digits Sensor monitoring: hardware diagnostics of sensor breakage Galvanic isolation: 2500 V Interference coefficient: normal/general type interference attenuation coefficient with frequency50 Hz - not less than 98/120 dB Temperature: operating temperature range from -40 to +70 C Connection interface: RS-485 Ranges and types of thermocouples: independent setting of thermocouple type for each channel Protocols: default protocol - DCON and MODBUS RTU (enabled by software) Power supply: from 10 V to 30 V Power consumption: not more than 0.5 W Mounting: on DIN-rail Dimensions (HxWxG): 123x76x33 mm Warranty: 18 months
Specifications
Flammability class according to GOST 28157 (UL 94)
NV
Operating conditions
operating temperature range from -40 to +70 °C
Size
123x76x33
Assignment
for measuring thermocouple signals
Material
ABS plastic impact resistant